The
economic OZH100 system provides you with revolutionary value and
performance in addressable sensing technology, reduces nuis
Product
Overview
The
OZH100 control panel is an analog addressable fire alarm panel using
the latest microprocessor technology and containing one SLC loop
supporting 252 devices of any combination (sensors or modules).
Communication between devices is transferred through standard cable
(shielded or twisted pair is not required). Each panel includes a 3.0
amp power supply, large screen LCD display, 25 large easy-to-use
tactile touchpad for system operation, programming and maintenance and
12 state indicators. System operations include silencing alarms and
troubles, resetting system and manual starting/stopping field
equipment. The system’s non-volatile event history buffer stores 999
events for viewing. The system supports a variety of Orena devices:
smoke and heat sensors, manual call points, contact input (monitor)
modules, relay output modules, dual input/output modules, and short
circuit isolator modules. In addition, interfaces to conventional
detection systems can be established by using a conventional
zone-monitoring module. The basic system can be expanded by adding
OZF-LCD2 remote annunciator. The intelligent panel and detectors know
the difference between a fire and a dirty sensor. It lets you tailor
sensor sensitivity and gives you immediate, pinpoint accuracy for any
condition. The economic OZH100 system provides you with revolutionary
value and performance in addressable sensing technology, reduces
nuisance alarms and makes service calls a rarity.
Characteristics
•
Using advanced industry-standard protocol for fast and stable
communication
•
Connect with 252 addressable points ( any mix of sensors &
modules & call points) in one
loop
•
Uses standard wire, no shielded or twisted pair required on SLC loops
•
Supports Class B (style 4) and Class A (style 6 or 7) SLC loops
•
Automatic drift compensation & daily calibration
•
Programmable sensitivity levels per device
•
Large 4-line x 22-character LCD display (88 char.)
•
Built-in help information screens
•
2.5A of auxiliary power available rated at 24 VDC
•
Field-programmable on panel
•
Powerful & versatile Cause & Effect programming (fire
protection-related device control)
•
Extensive, built-in transient protection
•
Surface Mount Technology (SMT) electronics
Specifications
Primary
Power Supply: 120V or 220VAC 50/60Hz
Standby
Batteries: DC24V 2.2AH sealed rechargeable batteries
Power
Supply Output: 24VDC @ 3.0 Amps (2.5 Amps available for system power)
Display:
4 lines x 22 characters LCD (88 characters total)
SLC
loops: Class A, “style 6 or 7” or class B, “style 4”
Devices
per loop: 252 sensors & modules & call points
Operation
Temperature: –10°C~+50°C Related Humidity: ≤95% (40±2°C)
Dimensions
(D * W * H): 60×370×240mm
Weight:
3.5Kg
SLC
DEVICES & SYSTEM ACCESSORIES
MODEL
DESCRIPTION
OT602
Analogue Addressable Photoelectric Smoke Detector
OT603
Analogue Addressable Heat Detector
ODZ6004
4 inch Addressable Detector Base
OA610
Addressable Manual Call Point
OX620
Addressable Hydrant Button (waterproof)
OS631
Addressable Horn & Strobe
OM611
Addressable Supervised Relay Module
OM621
Addressable Dual Relay Output Module
OM612
Addressable Input Monitor Module
OM622
Addressable Dual Input Monitor Module
OM613
Conventional Zone Monitoring Module
OM515
Short Circuit Isolator Module
OMDZ51
Module Base
OBM
Hand Held Programmer (portable device addresser)
OZF-LCD2
LCD Remote Annunciator