Product
Overview
The
ODH08E Conventional Fire Alarm Control Panel is a 24volt, 8, Class B,
Conventional Fire Alarm Control Panel. It is designed exclusively to
meet the latest market requirements and microprocessor technology, with
stand-by batteries (two sealed acid storage batteries) and reserved
space for installation. It has functions of operation indication, fault
indication, alarm indication and cable checking for short circuit or
broken circuit. The highly cost-effective ODH08-16 can be used in
low-sized applications.
Characteristics
1) Style
B (Class B) Initiating Device Circuits (IDCs) accept two-wire smoke
detectors and any normally-open contact devices
2)
One set of volt free changeover contacts operable on fire
3) One
set of volt free changeover contacts operable on fault
4) Non-latching
zones facility
5)
Class change input for remote control
6)
Zone and alarm disablement
7)
28V 125mA fused supply permanently available
8)
28V 300mA fused supply available for fire alarm bells or sounders
9)
Passive repeater available
Specifications
AC
Power: AC220V±10% 50Hz, 2.0 amps, minimum 14 AWG wire (2.0 mm²) with
600-volt insulation.
Battery:
Sealed lead-acid batteries, Maximum battery charger capacity: 4AH
battery
Total
24 V system power: 3.0 amps
Zone
Capacity: can be connected with 30 fire detectors and infinite manual
call points
Fire
& Fault Contact Outputs: 1.0 amps DC24V or AC125V
Using
environment: Temperature: 0°C~50°C Related Humidity: ≤95% (40±2°C)
Dimensions:
265×335×87mm (length × width × depth)
There are no reviews yet.